- Detail
Operating environment conditions
◇ Ambient temperature: -40° C to +40° C;
◇ Altitude: Not exceeding 3000 metres;
◇ Power supply frequency: 48Hz to 62Hz;
◇ Maximum wind speed: Not exceeding 35 metres per second;
◇ Seismic intensity: Regions rated 7 degrees or below.
Model meaning

Installation and user guide
◇ This product should be installed on circuits of systems and equipment with a rated voltage matching that of the surge arrester.
◇ Before installation and use, check the tightness of the connection between the surge arrester element and the drop-outmechanism to ensure good contact and smooth operation.
◇ Adjustment method: Rotate the copper contact (with pull ring) on the surge arrester so that the opening force is within 6–10 kg, ensuring the pull ring side of the copper contact faces outwards. Then tighten the lower nut to prevent the pull ring from rotating.
◇ During installation, the surge arrester should be positioned at an angle of 15–30 degrees to the plumb line, with a minimum distance of 200 mm.
Principal technical parameters
| Surge arrester model | System rated voltage kV(r.m.s) | Surge arrester rated voltage kV(r.m.s) | Continuous operating voltage kV(r.m.s) | DC reference voltage ≮ kV | 0.75U1mA leakage current ≯ μA | Residual voltage under lightning impulse current ≯ kV | Residual voltage under operating surge current ≯ kV | Square wave current capacity (2ms) ≮ A | High-current surge withstand capability ≮ kV | Place of use |
| HY5WS-10/30DL | 6 | 10 | 8.0 | 15.0 | 30 | 30 | 25.6 | 150 | 40 | Power distribution |
| HY5WS-10/30DL-TR | ||||||||||
| HY5WS-10/30DL-TB | ||||||||||
| HY5WS-17/520DL | 10 | 17 | 13.6 | 25.0 | 30 | 50 | 42.5 | 150 | 40 | Power distribution |
| HY5WS-17/50DL-TR |
Note: The parameters of the surge arrester are identical to those of a conventional surge arrester. The above specification pertains to the distribution type; it may be substituted with capacitive or other types.
Product structure overview