ZW43-12 Outdoor High-voltage Vacuum Circuit Breaker

The ZW43-12(G) type outdoor high-voltage vacuum circuit breaker (hereinafter referred to as the switch) is an outdoor high-voltage switchgear for three-phase AC 50Hz with a rated voltage of 12kV. The switch is mainly used as a 10kV outgoing switch in substations and as a line protection switch in 10kV-level three-phase AC power systems for making or breaking load current, interrupting overload current, and short-circuit current.
  • Detail

Overview

The ZW43-12(G) type outdoor high-voltage vacuum circuit breaker (hereinafter referred to as the switch) is an outdoor high-voltage switchgear for three-phase AC 50Hz with a rated voltage of 12kV. The switch is mainly used as a 10kV outgoing switch in substations and as a line protection switch in 10kV-level three-phase AC power systems for making or breaking load current, interrupting overload current, and short-circuit current. 

The circuit breaker complies with technical standards such as GB1984-2003 "High-Voltage AC Circuit Breakers", DL/T402-2007 "Technical Conditions for Ordering High-Voltage AC Circuit Breakers", and DL/T403-2000 "Technical Conditions for Ordering 12kV~40.5kV High-Voltage Vacuum Circuit Breakers".


Model Meaning

1-1.jpg


Operating Environment

1. Ambient air temperature: upper limit 40℃, lower limit -40℃;

2. Altitude: not exceeding 3000 m;

3. Wind pressure: not exceeding 700 Pa (equivalent to wind speed of 34 m/s);

4. Air pollution level: not exceeding Class IV;

5. Ice thickness: not exceeding 10 mm;

6. No fire, explosion hazard, chemical corrosion, or severe vibration.


Main Technical Parameters

No.ItemUnitParameter
1Rated VoltagekV12
2Rated Insulation Level1min Power Frequency Withstand Voltage Dry test, to ground, between poles/open gapkV42/48
Wet test34
 Lightning impulse withstand voltage, peak, between poles/open gap75/85
3Rated CurrentA630
4Rated Short-Circuit Breaking CurrentkA20
5Rated Operating SequenceO-0.3-CO-180S-CO
6Rated Short-Circuit Breaking Current Breaking TimesTimes30
7Rated Short-Circuit Making Current (Peak)kA50
8Rated Peak Withstand CurrentkA20
9Rated Short-Circuit Durations4
10Opening Time (From control unit receiving opening command to three-phase contacts separation)s0.040~0.060
11Closing Time (From control unit receiving closing command to three-phase contacts closing)s0.070~0.120
12Mechanical LifeTimes10000
13Rated Closing Operating VoltageVDC110, DC220
14Rated Opening Operating VoltageVDC110, DC220
15Overcurrent ProtectionCurrent Setting MultiplesS0.2~2.5
Setting Current Tolerance±10%
16Delay Setting Value0~5
Delay Tolerance±10%
Current Setting Multiples2.5~10
17Instantaneous ProtectionSetting Current ToleranceS±10%
Delay Setting Value0~0.5
Delay Tolerance±10%
18Rated Value of AC Charging for Control UnitRated valueA5
Input CurrentRange of fluctuation0.5~8


Appearance and Installation Dimensions

2-1.jpg