- Detail
Overview
The ZW32H(T)-12 type outdoor high-voltage AC vacuum circuit breaker adopts the vacuum arc extinguishing principle and a permanent magnetic operating mechanism (spring operating mechanism), integrating microprocessor technology, modern network communication technology, and new switch manufacturing materials. It is an outdoor distribution device with a rated voltage of 12kV and 50Hz three-phase AC. This product is widely used in urban power grids as a disconnecting or tie switch, or in rural power distribution systems. As an outgoing line switch in outdoor substations, it can effectively perform the functions of a traditional recloser, breaking and closing load current and short-circuit current.
Model Meaning

Operating Environment
1. Ambient air temperature: -40℃ to 55℃, daily temperature variation: 25K;
2. Altitude: not exceeding 2000m;
3. Wind speed: not exceeding 35m/s;
4. Pollution level: Class IV;
5. Installation location: free of flammable, explosive hazards and chemical corrosion;
6. Seismic intensity not exceeding 8 degrees;
Main Technical Parameters
| Serial No. | Item | Unit | Data |
| 01 | Contact Gap | mm | 9±1 |
| 02 | Contact Overtravel | mm | 2 |
| 03 | Opening Speed | m/s | 1±0.2 |
| 04 | Closing Speed | m/s | 0.6±0.2 |
| 05 | Contact Closing Bounce Time | ms | ≤2 |
| 06 | Phase Center Distance | mm | 340±1.5 |
| 07 | Three-Phase Opening/Closing Asynchrony | ms | ≤2 |
| 08 | Three-Phase Conductor Circuit Resistance | μΩ | <80 (Excluding disconnector and CT) |
| 09 | Closing Time | ms | 30-80 |
| 10 | Opening Time | ms | 23-45 |
| 11 | Weight | kg | Approx. 105 |
Appearance and Installation Dimensions