VZF-12R Sealed Vacuum Load Switch-Fuse Combination Device

The VZF-12R center-mounted, sealed vacuum load switch-fuse combination device (hereinafter referred to as the vacuum switch) is a vacuum switch device developed based on a special design concept and market demand. It is widely used in indoor metal-clad air-insulated switchgear and complies with standards such as GB3804-2004 and GB16926-1997.
  • Detail

Overview

The VZF-12R center-mounted, sealed vacuum load switch-fuse combination device (hereinafter referred to as the vacuum switch) is a vacuum switch device developed based on a special design concept and market demand. It is widely used in indoor metal-clad air-insulated switchgear and complies with standards such as GB3804-2004 and GB16926-1997. 

Under normal operating conditions, as long as it operates within the technical parameter range of the vacuum switch, the VZF-12R center-mounted, sealed vacuum load switch-fuse combination device can ensure safe and reliable operation within power grids of the corresponding voltage level.


Model Meaning

1-1.jpg


Operating Environment

1. Ambient temperature: maximum temperature 40℃, minimum temperature -25℃.

2. Ambient humidity: daily average relative humidity: ≤ 95%, monthly average relative humidity: ≤ 90%.

3. Daily average saturated vapor pressure: ≤ 2.2x10^-3 MPa.

4. Monthly average saturated vapor pressure: ≤ 1.8x10^-3 MPa.

5. Altitude: not higher than 1500 m.

6. Seismic intensity: not exceeding 8 degrees.

7. Applicable locations: no dripping water, no fire or explosion hazards, no chemically corrosive gases, no severe vibration.

8. If the product's usage environment exceeds the above specifications, the user can negotiate with our company for confirmation.


Main Technical Parameters

No.ItemUnitVZF-12/T630-20
Vacuum Load Switch
Vacuum Load Switch - Fuse Combination Appliance
VZF-12/T125-50
01Rated VoltagekV1212
021min Power Frequency Withstand Voltage (Between Phases, to Ground)kV4242
03Lightning Impulse Withstand Voltage (Between Phases, to Ground)kV7575
04Rated CurrentA630125 (Fuse)
05Rated Short-Circuit Breaking CurrentkA-50 (Fuse)
06Rated Short-Time Withstand CurrentkA20-
07Rated Peak Withstand CurrentkA50-
08Rated Short-Circuit Making CurrentkA50-
09Rated Cable Charging Breaking CurrentA16-
10Rated Transfer CurrentA-3150
11Breaking No-Load TransformerkVA1250-
12Battery LifeTimes10000
13Partial Discharge LevelpC≤ 5